OLMO - R410A - 22 - 2 - 3 zones - Outdoor Condenser - Sierra - 208-230V

Regular price $974.00 USD
Regular price $1,605.00 USD Sale price $974.00 USD
Sale Sold out
Shipping calculated at checkout.
Quantity
View full details

Product Overview

OLMO logo

OLMO Multi-Sierra 24,000 BTU Outdoor Heat Pump — OS-MSR24-230VO

Multi-zone inverter heat pump for 2–3 zones. Up to 22 SEER2 and 12.5 EER2. Designed for Multi-Sierra wall-mount indoor units.

24,000 BTU/h cool & heat 2–3 zones SEER2 up to 22 EER2 up to 12.5 R410A 208–230V, 1Ph, 60Hz

Why pros choose this outdoor unit

  • Flexible zoning: supports 2 to 3 indoor units.
  • High efficiency: up to 22 SEER2 with inverter technology.
  • Cold-climate operation: heating down to −13°F per spec range.
  • Simple electrical: MCA 25 A, max fuse 30 A.
At-a-glance
Model
OS-MSR24-230VO
Zones
3-4 Zones
Refrigerant
R410A
Sound
59 dB(A)

What’s included

  • Outdoor inverter heat pump unit OS-MSR24-230VO
  • Owner/installation documentation (per shipment)

Indoor units, line sets, communication cable, and accessories sold separately.

Tech specs

OS-MSR24-230VO — Technical specifications
Voltage range (V) 198~253
System type Multi-zone unit
SEER2 up to 22
Refrigerant type R410A
Refrigerant piping Liquid/Gas side (inch) 1/4"/3/8"
Packing dimensions (WxDxH) 43-3/4x18-1/8x36-1/4
Max. pipe length (ft) 66/197
HSPF2-5 9.17
HSPF2-4 11.21
EER2 up to 12.5
Unit Net/Gross weight 158.7/169.5
Unit dimensions (W*H*D) 37-3/8x33x13-3/8
Power source 208-230V, 1Ph, 60Hz
Outdoor Noise Level 59
Minimum circuit ampacity 25
Max.fuse 30
Heating Capacity at 47°F 24,000
COP 3.66
Cooling Capacity (nominal) 24,000
Ambient temperature - Heating -13~75.2
Ambient temperature - Cooling 14~114.8
Outdoor air flow (CFM) 2350

Confirm port count, line sizes, and charging against the submittal and installation manual for your zone mix.

Warranty

  • 5-year compressor limited warranty
  • 2-year parts limited warranty (licensed HVAC install and registration within 60 days)

FAQs

How many rooms can this support?
Two to three zones when paired with compatible Multi-Sierra wall-mount indoor units.
What refrigerant does it use?
R410A with factory precharge. Add charge per line length as specified.
What electrical protection is required?
MCA 25 A and max fuse 30 A at 208–230 V single phase. Follow local code.
What are the operating temperature ranges?
Heating −13~75.2°F. Cooling 14~114.8°F.